FD-PAO1

Low-Voltage Power Supply Module 6 units DIN rail

FD-PA01 Front

Functional characteristics

The FD-PA01 is a power supply module with back-up battery, It has the following characteristics:
•  Designed for mounting on DIN rail
•  Able to supply 12V 1.3A
•  Able to supply field devices for more than 4 hours when linked to a lead battery with 12V 7.5Ah capacity
•  Battery disconnection at 10V for over-discharge protection
•  Output can be connected in parallel with other power supplies
•  Able to monitor all electrical parameters, including battery efficiency tests, through a special connection to the FD-DA01 module
•  Visual On/Off indicator for main power supply
•  Fault and/or overload indicator
•  Connection to FD-BUS through an RJ45 connection
Double connector (internally in parallel) for easy reconnection to the FD-BUS.

Protection

The equipment is protected against the following events:
•  polarity reversal on the cables (RJ45) connecting to the FD-BUS
•  voltage surge in the incoming power supply
•  temporary short-circuit on the output

Modes of Operation

The FD-PA01 module supplies the power for the Orangelink system.
•  In limited monitoring mode (for access control and attendance registration), power is supplied directly to the Orangelink devices through the FD-BUS outputs and/or through the output terminal.
•  In the extended monitoring mode (for intrusion protection, access control and attendance registration) power is supplied through the output terminal only, and one of the FD-BUS connectors is used to supply the remote monitoring signals to an FD-DA01 module.

Visual indicators

The FD-PA01 module can give the user indications by means of:
•  a red LED
•  a green LED

The most common indications are as follows:
•  Green LED, lit steadily when main power is On
•  Green LED, flashing when main power is Off
•  Red LED, flashing in the event of an overload (overvoltage or overcurrent)
•  Red LED, lit steadily in the event of a fault (no voltage at output) or if power is about to go off.All indicator signals are generated locally.

Technical specifications

Power Supply

Power consumption (for Iout=1.5A)
1.5A (battery charged) to 3A (battery discharged) at 24VCA
2.0A (battery charged) to 3A (battery discharged) at 18VCA

Input voltage
18VCA to 25VCA (with AC power supply)
24VDC to 35VDC (with DC power supply)

Output voltage
13VDC to 14VDC (main power supply)
10VDC to 13VDC (battery supply)

Output current
Up to 1.3A (overload alarm at 1.5A)

Fuses
Input fuse: 3.15A 250V T (5x20)
Battery fuse: 3.15A 250V T (5x20)

Interface Hardware

Indirect terminal blocks for cables up to AWG12
•  DC/AC power input
•  Battery
•  Power output
•  Connections for RJ45 cables
•  Connectors for FD-BUS (2 RJ45s in parallel)

Physical Characteristics

•  Working temperature: 0 to 40°C (ventilation by natural convection)
•  Humidity: up to 95% without condensation
•  Dimensions: 105x85x55mm (6 DIN units)
•  Weight: 250g
•  Mounting: horizontally on DIN rail with no obstructions at the ventilation slots

Request more information

If you would like more information on this product please fill in this form. Please make sure you include your name and contact details or we will not be able to get back to you.

Information request on: FD-PAO1

*Required field










 Data Collection Terminals
 Access Control Systems
 Time & Attendance Systems



Privacy Statement. Zucchetti Axess guarantees that the information you submit will be treated in the strictest confidence and in accordance with Italian legislation on data management (Legislative Decree n. 196 of 30 giugno 2003).

gototop

Search this site